4 × 5000 m³ LNG storage tanks
Product Details
4×5000m³ LNG storage tanks
With the development of the LNG industry, LNG storage is becoming larger and operating at normal pressure. Domestic design and manufacturing have reached 50,000m³, and single units of 250,000m³ and 160,000m³ LNG normal pressure storage tanks have been established along the coast to receive ship-borne LNG.
Currently, the LNG storage tanks designed, manufactured, and installed in China are mainly 5,000m³ and 10,000m³, widely used in LNG liquefaction plants or LNG peak shaving stations. The amount of LNG produced from industrial waste gas is generally small, and 1,000m³ LNG storage tanks are commonly used.
Product Details
Main Structure Type
Vertical cylindrical, double-walled, flat bottom, arched top (200~50000m³), above 6000m³ is a floating roof type (self-supporting ceiling).
Insulation Method: Double-walled powder accumulation insulation
Basic Form: High platform type
Process System
01. Purging System
02. Liquid Inlet System
03. Liquid Discharge System (External and Submerged)
04. Pump Backflow System
05. Interlayer Nitrogen Supply System
06. Liquid Level and Pressure Measurement System
07. Temperature Measurement System
08. Gas Emission System
09. BOG Pipeline System
10. Analysis and Sampling System
11. Safety System
12. Pressure Stabilization System
13. Firefighting System
Foam Glass Brick Introduction
● Lightweight, around 150KG/m³;
● Low thermal conductivity, below 0.050W/m*k (38℃), stable thermal performance;
● Moisture-proof
● Low water absorption, about 0.2%
● Non-combustible;
● No mold or corrosion;
● High strength, compressive strength ≥0.8MPa, can withstand acidic corrosion (except hydrofluoric acid);
● Non-toxic, contains no CFCs (chlorofluorocarbons) or HCFCs (hydrochlorofluorocarbons);
● Stable physical and chemical properties, dimensionally stable.
LNG Storage Tank Design, Manufacturing, and Acceptance Standards
● European Standard BS EN 14620 "Design and On-site Manufacturing of Vertical, Cylindrical, Flat-bottomed Cryogenic Storage Tanks Operating at Temperatures Between 0℃ and -165℃"
● JB/T 9077-1999 "Powder Ordinary Insulation Storage Tanks"
● JB/T 4735-1997 "Steel Welded Normal Pressure Vessels"
● American Standard API 620 "Design and Construction of Large Welded Low-Pressure Storage Tanks"
● JB/T 4730-2005 "Non-destructive Testing of Pump Pressure Equipment"
● GB 50128-2005 "Construction and Acceptance Specifications for Vertical Cylindrical Steel Welded Storage Tanks"
● GB/T 20368-2006 "Liquefied Natural Gas (LNG) Production, Storage, and Transportation"
Key words: